Model |
Evolution |
Evolution S |
650 |
850 |
1150 |
1550 |
2000 |
1250 |
1750 |
2500 |
3000 |
Rating |
650 VA 420 W |
850 VA 600 W |
1150 VA 770 W |
1550 VA 1100 W |
2000 VA 1600 W |
1250 VA 1150 W |
1750 VA 1600 W |
2500 VA 2250 W |
3000 VA 2700 W |
Format |
Tower or 1U Rack |
RT2U (tower/rack 2U) |
RT2U & RT3U |
Electrical characteristics |
Technology |
Line Interactive High Frequency (Booster + Fader) |
Input voltage and frequency ranges wtihout using batteries |
160V - 294V (adjustable to 150 - 294V) 47 to 70 Hz ( 50Hz system), 56,5 to 70 Hz (60Hz system) (1) |
Ouput voltage and frequency |
230 V (+6/-10%)(2), 50/60Hz +/-0,1% |
Connections |
Input |
1 IEC C14(10A socket) |
1 IEC C20 (16A socket) |
Outputs |
4 IEC C13 (10A) |
8 IEC C13 (10A) |
8 IEC C13 (10A) sockets IEC C19 (16A) socket |
Remotely controlled sockets |
2 groups of 1x IEC C13 (10A) |
2 groups of 2 x IEC C13 (10A) |
Additional outputs with HS MBP |
4 FR / Schuko sockets or 3 BS socketsor 6 IEC 10 A sockets or terminal blocks (HW version) |
Additional outputs with FlexPDU |
8 FR/Schuko sockets or 6 BS sockets or 12 IEC 10 A sockets |
Batteries |
Typical backup times for 50 and 70% of the VA |
Evolution / Evolution S |
9/6 mn |
16/7 mn |
14/7 mn |
14/7 mn |
14/7 mn |
20 /14 mn |
14 /9 mn |
17 /11 mn |
15 /10 mn |
Evolution S + 1 EXB |
- |
105 /60 mn |
60 /36 mn |
85 /55 mn |
60 /42 mn |
Evolution S + 4 EXB |
- |
300 /200 mn |
180 /115 mn |
290 /200 mn |
210 /135 mn |
Battery management |
Automatic weekly test (period adjustable), automatic recognition of external battery units => continuous maximization of backup time + deep discharge protection |
Interfaces |
Communication ports |
1 USB port + 1 RS232 serial port and relay contacts (3)+ 1 mini terminal block for remote ON/OFF and Remote Power Off |
Communications card slots |
1 slot for NMC Minislot 2006 card (included in Netpack versions) or NMC ModBus/JBus or MC Contacts/ serial |
Operating conditions standards and approvals |
Operating temperature |
0 to 35°C |
0 to 40 °C |
Noise level |
< 40 dbA |
< 45 dbA |
< 50 dbA |
Performance - Safety - EMC |
IEC EN 62040-1-1 (Safety), IEC/EN 62040-2 EN 50091-2 class B(EMC),IEC/EN 62040-3 (Performance), IEC EN 61000-4-2, 61000-4-3, 61000-4-4, 61000-4-5, 61000-4-6, 61000-4-8 (EMI) |
Approvals |
CE, CB report, TUV, cTUVus |
Dimensions (WxDxH) in mm/Weight in kg |
Dimensions of the Tower |
147 x418 x234 |
147 x492 x234 |
440 x509 x86.2 (2U) |
440 x634 x86.2 (RT2U) 440x 484 x130.7 (RT3U) |
Dimensions of the Rack |
438 x366 x43.2(1U) |
438 x512 x43.2 (1U) |
438 x556 x43.2 (1U) |
Weight of the Tower/Rack |
8.4 /10.1 |
10.85 /16.1 |
12.5 /16.6 |
16.53 /20 |
25.7 |
24.3 |
26.6 |
33.8 |
33.8 (RT2U) 34.3 (RT3U) |
Dimensions of EXB |
- |
440 x509 x86.2 (2U) |
440 x484 x130.7 (3U) |
Weight of the EXB |
- |
30.4 |
41.7 |